Carlo Gavazzi
RGC2A60A75GGEAFM2P -SSC-AC IN-ZC 600V 3X75A 1200VP-E-CLP IN MNTR
2P -SSC-AC IN-ZC 600V 3X75A 1200VP-E-CLP IN MNTR
Solid State / Static Relay (SSR) with integrated heatsnk. + integrated fan + contact. connection configuration + monitoring system + EMR alarm output - Carlo Gavazzi (RGC2 series) - Output 75A (AC; 15000A²s) / 90Vac-660Vac (600Vac nom.) - zero-cross switching (ZC) - 20-275Vac (24Vac / 120Vac / 220Vac / 240Vac nom.) control voltage - 2 switching poles + 1 direct pole (3P) - Supply voltage 90-250Vac (110Vac / 120Vac / 240Vac nom.; external supply) - box-clamp connections (control & pwr. connections) - with over-temperature protection
Please add this item to cart to request a quote or contact us at [email protected] for product availability.
Brand
SKU
RGC2A60A75GGEAFM
Please add this item to cart to request a quote.
Please add this item to cart to request a quote or contact us at [email protected] for product availability.
Minimum quantity may be required
Carlo Gavazzi - RGC2-A75-AFMRGC2A60A75GGEAFM
Description
Solid State / Static Relay (SSR) with integrated heatsnk. + integrated fan + contact. connection configuration + monitoring system + EMR alarm output - Carlo Gavazzi (RGC2 series) - Output 75A (AC; 15000A²s) / 90Vac-660Vac (600Vac nom.) - zero-cross switching (ZC) - 20-275Vac (24Vac / 120Vac / 220Vac / 240Vac nom.) control voltage - 2 switching poles + 1 direct pole (3P) - Supply voltage 90-250Vac (110Vac / 120Vac / 240Vac nom.; external supply) - box-clamp connections (control & pwr. connections) - with over-temperature protection
Additional Information
Solid state / static relay (SSR) - 3-phase - Carlo Gavazzi (RGC2) - Rated current 75A - Control voltage 20-275Vac - Rated voltage 600Vac - with Fan / Fault Monitoring. RGC2A60A75GGEAFM 1021419
Specifications
Primary brand
Carlo Gavazzi
Main function
Solid State Relay (SSR)
Product series / family name
RGC2 series
Functions
Solid State / Static Relay (SSR)
Design
integrated heatsnk.
integrated fan
contact. connection configuration
monitoring system
EMR alarm output
zero-cross switching (ZC)
integrated fan
contact. connection configuration
monitoring system
EMR alarm output
zero-cross switching (ZC)
Poles
2 switching poles + 1 direct pole (3P)
Supply voltage (AC)
90-250Vac (110Vac / 120Vac / 240Vac nom.; external supply)
Display
green LED indicator (control-ON)
Rated current
75A (AC; 15000A²s)
75A (AC at Ta = 40°C; AC-51; induction-free or slightly inductive loads / resistance furnaces)
28A (AC at Ta = 40°C; AC-53a; control of a squirrel cage motor; 8-hour operation with starting currents for starting processes / maneuvering / operation)
Minimum operational current 1.2A (AC). Relay output will not conduct below this value
Repeating overload current t-on=1s t-off=9s 154A (AC)
Maximum transient surge current t=10ms 1750Apeak
Minimum I²t for fusing t=10ms ≤15000A²s
75A (AC at Ta = 40°C; AC-51; induction-free or slightly inductive loads / resistance furnaces)
28A (AC at Ta = 40°C; AC-53a; control of a squirrel cage motor; 8-hour operation with starting currents for starting processes / maneuvering / operation)
Minimum operational current 1.2A (AC). Relay output will not conduct below this value
Repeating overload current t-on=1s t-off=9s 154A (AC)
Maximum transient surge current t=10ms 1750Apeak
Minimum I²t for fusing t=10ms ≤15000A²s
Rated voltage (AC)
90Vac-660Vac (600Vac nom.) output voltage
45-65Hz
PF / cos phi ≥0.5 (inductive load)
1200Vac (Vp; output blocking voltage)
ON-state voltage drop ≤2Vac (at rated current)
Rated impulse withstand voltage; Uimp 6kV (1.5/50μs)
45-65Hz
PF / cos phi ≥0.5 (inductive load)
1200Vac (Vp; output blocking voltage)
ON-state voltage drop ≤2Vac (at rated current)
Rated impulse withstand voltage; Uimp 6kV (1.5/50μs)
Connection type
box-clamp connections (control & pwr. connections)
Control Voltage (AC)
20-275Vac (24Vac / 120Vac / 220Vac / 240Vac nom.)
Control Voltage (DC)
Pick-up voltage 20Vac
Drop-out voltage 5Vac
Drop-out voltage 5Vac
Protection functions
over-temperature protection
Mounting mode
direct screw mounting on surface
Speed
Max. response time 5 cycles at 230Vac
Critical dV/dt 1000V/μs
Critical dV/dt 1000V/μs
Digital outputs
1 x digital output (SPDT / Form C rly. contact; 2A at 250Vac / 30Vdc) (alarm output)
Degree of protection
IP20
Dimensions
70mm width
Order code / Manufacturer SKU
RGC2A60A75GGEAFM
Manufacturer product status
Commercialized
Compliant with standard(s)
LVD (EN/IEC 60947-4-2; EN/IEC 60947-4-3)
EMCD (EN 60947-4-3)
UL 508 Listed (E172877)
cUL (C22.2 No.14-13; E172877)
CCC; GB/T 14048.5-2017 (IEC 60947-5-1)
VDE 0660-117 (DIN EN 60947-4-2)
CE
EAC
EMCD (EN 60947-4-3)
UL 508 Listed (E172877)
cUL (C22.2 No.14-13; E172877)
CCC; GB/T 14048.5-2017 (IEC 60947-5-1)
VDE 0660-117 (DIN EN 60947-4-2)
CE
EAC
Benefits
This product is intended to replace mechanical contactors especially when switching is frequent.
The smallest product width in the RGC2 RGC3 range is 54mm (3xDIN) and goes up to 70mm.
2-pole and 3-pole switching options are available.
Apart from resistive and slightly inductive loads the RGC is certified for motor switching with associated motor ratings.
A green LED gives indication of control voltage presence.
Fan operation is controlled for the versions which have an integrated fan.
Detection of SSR overheat mains loss SSR malfunction and load loss is possible with the RGC..M versions.
An EMR alarm output is available for remote signaling.
An additional feature with the RGC..M is the electronic auxiliary output.
The RGC..M has additional LEDs for load status and alarm status indication.
The smallest product width in the RGC2 RGC3 range is 54mm (3xDIN) and goes up to 70mm.
2-pole and 3-pole switching options are available.
Apart from resistive and slightly inductive loads the RGC is certified for motor switching with associated motor ratings.
A green LED gives indication of control voltage presence.
Fan operation is controlled for the versions which have an integrated fan.
Detection of SSR overheat mains loss SSR malfunction and load loss is possible with the RGC..M versions.
An EMR alarm output is available for remote signaling.
An additional feature with the RGC..M is the electronic auxiliary output.
The RGC..M has additional LEDs for load status and alarm status indication.
Degree of pollution
2
Related Documents
Name | Last Update | Language |
---|---|---|
Carlo Gavazzi - SSR - RGC2A - RGC3A.pdf | 12 Sep 2021 | English (US) |