Carlo Gavazzi
RGC3A60D25KKE3P -SSC-DC IN-ZC 600V 3X25A 1200VP-E-SRW IN
3P -SSC-DC IN-ZC 600V 3X25A 1200VP-E-SRW IN
Solid State / Static Relay (SSR) with integrated heatsnk. + contact. connection configuration - Carlo Gavazzi (RGC3 series) - Output 25A (AC; 1800A²s) / 42Vac-660Vac (600Vac nom.) - zero-cross switching (ZC) - 5Vdc-32Vdc (6Vdc / 12Vdc / 24Vdc nom.) control voltage - 3-switching poles (3P) - screw connections (control & pwr. connections) - DIN rail mounting (70mm width)
Please add this item to cart to request a quote or contact us at [email protected] for product availability.
Brand
SKU
RGC3A60D25KKE
Net Price
$430.00
Please add this item to cart to request a quote or contact us at [email protected] for product availability.
Minimum quantity may be required
Carlo Gavazzi - RGC3-D25RGC3A60D25KKE
Description
Solid State / Static Relay (SSR) with integrated heatsnk. + contact. connection configuration - Carlo Gavazzi (RGC3 series) - Output 25A (AC; 1800A²s) / 42Vac-660Vac (600Vac nom.) - zero-cross switching (ZC) - 5Vdc-32Vdc (6Vdc / 12Vdc / 24Vdc nom.) control voltage - 3-switching poles (3P) - screw connections (control & pwr. connections) - DIN rail mounting (70mm width)
Additional Information
Solid state / static relay (SSR) - 3-phase - Carlo Gavazzi (RGC3) - Rated current 25A - Control voltage 5-32Vdc - Rated voltage 600Vac - DIN Rail Mount - 1021429 RGC3A60D25KKE 3205808 SEL-5459 12217 095714-049 #instock
Specifications
Primary brand
Carlo Gavazzi
Main function
Solid State Relay (SSR)
Product series / family name
RGC3 series
Functions
Solid State / Static Relay (SSR)
Design
integrated heatsnk.
contact. connection configuration
zero-cross switching (ZC)
contact. connection configuration
zero-cross switching (ZC)
Poles
3-switching poles (3P)
Display
green LED indicator (control-ON)
yellow LED indicator (load-ON)
red LED indicator (alarm-ON)
yellow LED indicator (load-ON)
red LED indicator (alarm-ON)
Rated current
25A (AC; 1800A²s)
28A (AC at Ta = 40°C; AC-51; induction-free or slightly inductive loads / resistance furnaces)
11A (AC at Ta = 40°C; AC-53a; control of a squirrel cage motor; 8-hour operation with starting currents for starting processes / maneuvering / operation)
Minimum operational current 250mA (AC). Relay output will not conduct below this value
Repeating overload current t-on=1s t-off=9s 84A (AC)
Maximum transient surge current t=10ms 600Apeak
Minimum I²t for fusing t=10ms ≤1800A²s
28A (AC at Ta = 40°C; AC-51; induction-free or slightly inductive loads / resistance furnaces)
11A (AC at Ta = 40°C; AC-53a; control of a squirrel cage motor; 8-hour operation with starting currents for starting processes / maneuvering / operation)
Minimum operational current 250mA (AC). Relay output will not conduct below this value
Repeating overload current t-on=1s t-off=9s 84A (AC)
Maximum transient surge current t=10ms 600Apeak
Minimum I²t for fusing t=10ms ≤1800A²s
Rated voltage (AC)
42Vac-660Vac (600Vac nom.) output voltage
45-65Hz
PF / cos phi ≥0.5 (inductive load)
1200Vac (Vp; output blocking voltage)
Rated impulse withstand voltage; Uimp 6kV (1.5/50μs)
45-65Hz
PF / cos phi ≥0.5 (inductive load)
1200Vac (Vp; output blocking voltage)
Rated impulse withstand voltage; Uimp 6kV (1.5/50μs)
Connection type
screw connections (control & pwr. connections)
Control Voltage (DC)
5Vdc-32Vdc (6Vdc / 12Vdc / 24Vdc nom.)
Pick-up voltage 4.8Vdc
Drop-out voltage 1Vdc
Max. reverse voltage 32Vdc
Pick-up voltage 4.8Vdc
Drop-out voltage 1Vdc
Max. reverse voltage 32Vdc
Mounting mode
DIN rail mounting
Speed
Max. response time 0.5 cycle + 500μs at 24Vdc
Critical dV/dt 1000V/μs
Critical dV/dt 1000V/μs
Degree of protection
IP20
Dimensions
70mm width
Order code / Manufacturer SKU
RGC3A60D25KKE
Manufacturer product status
Commercialized
Compliant with standard(s)
LVD (EN/IEC 60947-4-2; EN/IEC 60947-4-3)
EMCD (EN 60947-4-3)
UL 508 Listed (E172877)
cUL (C22.2 No.14-13; E172877)
CCC; GB/T 14048.5-2017 (IEC 60947-5-1)
VDE 0660-117 (DIN EN 60947-4-2)
CE
EAC
EMCD (EN 60947-4-3)
UL 508 Listed (E172877)
cUL (C22.2 No.14-13; E172877)
CCC; GB/T 14048.5-2017 (IEC 60947-5-1)
VDE 0660-117 (DIN EN 60947-4-2)
CE
EAC
Benefits
This product is intended to replace mechanical contactors especially when switching is frequent.
The smallest product width in the RGC2 RGC3 range is 54mm (3xDIN) and goes up to 70mm.
2-pole and 3-pole switching options are available.
Apart from resistive and slightly inductive loads the RGC is certified for motor switching with associated motor ratings.
A green LED gives indication of control voltage presence.
Fan operation is controlled for the versions which have an integrated fan.
Detection of SSR overheat mains loss SSR malfunction and load loss is possible with the RGC..M versions.
An EMR alarm output is available for remote signaling.
An additional feature with the RGC..M is the electronic auxiliary output.
The RGC..M has additional LEDs for load status and alarm status indication.
The smallest product width in the RGC2 RGC3 range is 54mm (3xDIN) and goes up to 70mm.
2-pole and 3-pole switching options are available.
Apart from resistive and slightly inductive loads the RGC is certified for motor switching with associated motor ratings.
A green LED gives indication of control voltage presence.
Fan operation is controlled for the versions which have an integrated fan.
Detection of SSR overheat mains loss SSR malfunction and load loss is possible with the RGC..M versions.
An EMR alarm output is available for remote signaling.
An additional feature with the RGC..M is the electronic auxiliary output.
The RGC..M has additional LEDs for load status and alarm status indication.
Degree of pollution
2
Related Documents
Name | Last Update | Language |
---|---|---|
Carlo Gavazzi - SSR - RGC2A - RGC3A.pdf | 12 Sep 2021 | English (US) |